|
General
Problems
|
|
Symptom
|
Possible
Cause
|
Action
|
|
Valves are not opening
or not fully diverting the water flow.
|
1.
Load is too large for the transformer
2. Transformer
is burning out
3. Petroleum
or oil in system fluid causing the small EPDM O-ring seals to
swell.
|
1. Check
and add up the power draws or VA ratings of the valves supported
by the transformer. If
the combined VA rating of the valves is higher than the VA
rating of the transformer, change to a larger transformer or
split the system and add a second transformer. Note: Do not wire two transformers parallel.
2.
Change the transformer if secondary voltage is measured
too low (but not due to district low-line voltage supply) due to
faulty transformer.
3. Replace
adapter plate with plug seal and 0-ring seals.
Flush to clean the system and replace system fluid.
|
|
Burst pipe and/or burst
valve due to freeze ups.
|
1. Pipes
vulnerable to very low outdoor temperatures, e.g. located in
outside wall, near an open window, uninsulated etc.
2.
Occupant leaves door or window open to regulate room
temperature.
|
1.
Add pipe insulation or use a valve with internal let-by
that helps avoid freeze-ups by permitting a steady trickle of
water through the pipes.
2.
Keep doors and windows near pipes shut in winter or add
Outdoor Temperature Compensation control to hydronic system to
minimize over-heating problems.
|
|
Equipment seizes up.
|
Equipment sits idle
during long periods, e.g., summer.
The valve or the pump cylinder can seize up.
|
A knock of a hammer may
free the pump cylinder. If
that fails, replace the entire unit.
Install a control timer that “exercises” the pumps
and valves by regularly turning them on and off during the warm
months.
|
|
End switch failures.
|
Use of lubricating
silicone spray may have damaged the end switches.
|
Replace the valve
actuator. Avoid
using lubricating spray on actuators.
|
|
End switch does not make
connection.
|
1.
Insufficient supply of VA or voltage due to a faulty
transformer or due to an excessive drop in district line voltage
supply.
2. Too
many valves are powered by the same transformer.
3.
Failed switch contacts due to over current.
4. Valve
motor may be burned out or worn out.
5. Actuator
gear or motor gear may be worn out.
6. Valve
is installed backwards with respect to the flow direction.
|
1. Change the transformer
if it is faulty.
2. Add
or replace transformer.
3.
Ensure that the actual current draw is within the
specification of the end switch. Add isolating relay of the end
switch. Add isolating relay if current draw is too high.
4.
Replace valve motor.
5.
Replace Actuator.
6.
Reinstall valve Correctly.
|